| System name | NN100 | |
| Agent | 100% nitrogen | |
| Agent supply | Industrial use | |
| Design concentration (Vol %) |
40.3(classB) | 37.2(classA,C) |
| Agent quantity required | 0.52 m3/ m3 | 0.47 m3/ m3 |
| Cylinder pressure (MPa, at 40℃) |
30 | |
| Form of agent in storage | Vapor | |
| Secondary pressure (MPa, at 40℃) |
10.8 | |
| Piping class | Sch.80 | |
| Discharge time (sec.) |
60 | |
| Ozone depletion potential | 0 | |
| Global warming potential | 0 | |
| Toxicity | No | |
| Visual difficulties caused by the discharge of agent |
No | |